What is insulation resistance testing.
Cable insulation resistance test procedure.
Inspect exposed sections of cables and conductors for physical damage.
Applied potential shall be 500 volts dc for 300 volt rated cable and 1000 volts dc for 600 volt rated cable.
An insulation resistance test is typically performed on de energized wire and cable immediately after installation and before termination to any equipment or accessories.
This test is used to detect conductor insulation damage that may have been caused during installation.
The insulation resistance of cable is measured using a megohmmeter.
Insulation resistance testing is a non destructive test procedure.
Locate the connection point of the wire or cable you want to test so you have access to the exposed conductors.
Insulation resistance decreases in temperature or moisture.
7 3 2 2 2 2009.
With a little record keeping and common sense however you can get a good picture of the insulation condition from values that are only relative.
Sample insulation resistance megohmeter test connections for cable and transformer using guard terminal.
Replace or repair sections that exhibit damage.
When performing insulation tests on conductors and cable apply the following procedure.
Test duration shall be one minute.
Basically you re applying a voltage specifically a highly regulated stabilized dc voltage across a dielectric measuring the amount of current flowing through that dielectric and then calculating using ohm s law a resistance measurement.
Let s clarify our use of the term current.
A cable insulation test is basically a continuity test so the power to the circuit must be off.
The insulation resistance test is the second test required by the electrical safety testing standards.
Either turn off the breaker or if you re testing the wiring in a piece of equipment unplug it.
The insulation resistance test consists in measuring the insulation resistance of a device under test while phase and neutral are short circuited together.
If no literature from the manufacturer is available apply 500 volts dc for 300 volt rated cable and 1000 volts dc for 600 volt rated cable.
Perform an insulation resistance test on each conductor with respect to ground and adjacent conductors.
Inspect cables and conductors for proper grounding cable support and termination.
It is commonly used in the industry for acceptance testing prior to energizing the cable and for maintenance testing programs.
Test period must be for 1 minute using a voltage according to manufacturer s published data.
Developed early in the 20th century the insulation resistance ir test is the oldest and most widely used test for assessing the quality of insulation.
The test measures the insu lation resistance between the phases and or between phase and ground.
Perform insulation resistance test on each conductor with respect to ground and adjacent conductors.